1、Applicable scope and purpose Short circuit protection

Overload protection Isolation

Earth leakage

NDB2LM-63 series residual current protection module is used for protecting earth leakage, director indirect electric-shock on body and applied in low-voltage terminal distribution field, including

Industry, Civil Building, Energy, Communication and Infrastructure etc.

2、Model and implication:

No.ImplicationNDB2LM-63
1Brand codeND(Nader)
2Product codeB
3Design code2
4Earth leakage protectionL
5Electromagnetic typeM
6Frame rating(A)63
7Instantaneous tripping characteristicB,C,D
 8 Rated current(A)1,2,3,4,5,6,10,16,20,25,32,40,50,63
9Number of poles1P+N,2P,3P,3P+N,4P
10Rated residual operating current30mA,100mA,300mA
11Residual operating current typeA、AC
12level of sensitivityS
3、Main technical specifications
  • electric parameter
  • frequency:50/60Hz
  • Rated working voltage: AC230/240V (1P+N,2P) AC400/415V (3P,3P+N,4P)
    :AC110/120V(1P+N,2P)
  • Rated impulse withstand voltage:4kV
  • Rated insulation voltage:500V
  • Residual operating current type: A、AC
  • Instantaneous tripping characteristic: B、C、D
  • Rated current: 1A,2A,3A,4A,5A,6A,10A,16A,20A,25A,32A,40A,50A,63A
  • Rated breaking capacity: 10kA
  • Rated residual operating current: 30mA,100mA,300mA(regular);100mA,300mA(with time-delay)
  • level of sensitivity: Plain (not labeled), time delay (S)
  • Isolation function
  • Leakage is visible
  • Wiring
  • Tunnel type of wiring terminal
  • Connection area:1mm2~35mm2
  • Tighten screw torque: 3.5 N.M
  • Protection requirements
  • Protection grade:IP20
  • Protection grade for device which is installed in distribution box:IP40 5、Normal working environment
  • Height: ≤2000m, if you want to apply it more than 2000m, you must refer to Miniature Circuit Breaker’s reduced capacity table. Also you can refer to GB/T20645 the technological requirement of the low-voltage electrical equipment when it is usedon high altitude.
  • pollution degree:3
  • Ambient temperature:-25℃~+60℃
  • Stored ambient temperature: -40℃~+80℃
  • Humidity requirement: relative humidity under 40℃≤ 50%;
  • Magnetic requirement: magnetic field should be 5 times less than geomagnetic field in any directions
  • Sine wave distortion: le20s20s.0t4h.a29n 5%
  • Tolerate the influence of 试sa制lt mist and oil mist
  • Used in the place without explosion danger and the medium can’t have the corrosive action on metals and damage the insulation gas and conductive dust.
  • Used in the place without rain and snow.

4、 Tripping characteristic

  • B type curve
  • protect the non-inductive or micro-sense circuit
  • rated current: 1A~63A
  • tripping characteristic: instantaneous tripping range is 3In~5In
  • C type curve
  • protect normal load and distribution wire cable
  • rated current: 1A~63A
  • tripping characteristic: instantaneous tripping range is 5In~10In
  • D type
  • protect industrial distribution system
  • rated current: 1A~63A
  • tripping characteristic: instantaneous tripping range is 10In~14In

5、Outline and installation dimensions

1P+N

2P

3P

3P+N

4P

6、Installation Method

Installed in TH35mm x 7.5 standard guide rail and wired in tunnel type.

7、Packaging and storage

1P+N: 4pcs per box; 2P:3 pcs per box, 3P: 2pcs per box, 3P+N or 4P:1 pcs per box. Packing cartons should be stored where air circulation and relative humidity is not more than 50% and the tempera20t2u0r.e04.i2s9 not higher than + 80℃ and not less than – 40℃, and also  without  acidic alkaline  and  other  corrosive  gas. In  the  above  conditions, the

storage period since the production date is not more than three years.

8、Accessories list and installation

  • OF2 auxiliary contact: mount on the left side of MCB to indicate the tripping status of the associated MCB.
  • SD2 alarm contact: mount on the left side of MCB to indicate the fault tripping status of the associated MCB
  • MX+OF2 shunt tripping device: mount on the left side of MCB to remotely control MCB
  • NGQ2(A)Undervoltage tripping device: mount on the left side of MCB,  realize single-phase overvoltage, undervoltage, under-voltage protection function
  • Tm2 electric operating mechanism:mount on the left side of MCB to breaker on-off control
  • Tm2GQ Since multiple undervoltage: mount on the left side of MCB ,when in the light over-voltage or under-voltage, on line protection

9、Environmental protection requirement Conform to RoHS directive

10、Notice

  • No responsibility for problems caused by disassembling privately;
  • RCD can’t provide protection in the cases that touch two phase line synchronously;
  • Please don’t perform insulating resistance test or voltage-withstand test on the product

directly or indirectly by megohmmeter or similar test devices. If you need, we can offer validated proof regarding this item;

  • When testing insulating resistance of the engineering circuit, the RCD should not be connected to avoid misunderstanding on the products’ quality or damage its PCB;
  • Please make sure reliable connection to avoid fault tripping or damage of terminals caused by exceptional heat;
  • Simulating test should be made once a month by pressing the test button to check whether the circuit breaker works normally. If RCD is abnormal, it should be replaced.
  • If the RCD trip automatically, you must timely analyze the fault reason of the line or the device.
The prev: The next:

Related recommendations

  • NDM2L-630

    28

    1.Applicable Scope and Purpose of Circuit BreakerThe NDM2L-630 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infreque...

    View details
  • NDB2LE-40

    21

    Application Scope and Purpose Short-circuit protectionOverload protectionCurrent leakage Isolation The NDB2LE-40 series of residual current action&nb...

    View details
  • NDB1PT-63

    31

    1.Scope of application and use●Short-circuit protection●IsolationNDB1PT-63 series circuit breakers are applicable for the metering circuit, and can improve the electric energy metering precisi...

    View details
  • NDM2L-400

    18

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2L-400 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to inf...

    View details
Click Cancel to reply
    Expand more!
    咨询产品列表
    咨询产品列表 提交咨询以上产品
    咨询产品列表